B--65245EN/02
2. SIGNAL DESCRIPTIONSHANDLING
45
(1) Remaining travel in--range signal DEN2
[Classification]
Input signal <Xx+0#0> (common to both the peripheral equipment
control and direct command interfaces)
[Function]
This signal indicates that, in the servo amplifier unit, the number of
axis move command distribution pulses that have not been used for
axis movement (residual movement amount) is smaller than a
parameter--specified value.
[Input condition]
The signal becomes 1 when:
1. The number of axis move command distribution pulses t hat have
not been used for axis movement (residual movement amount) is
smaller than a parameter--specified value.
The signal becomes 0 when:
1. The number of axis move command distribution pulses t hat have
not been used for axis movement (residual movement amount) is
larger than a parameter--specified value.
2. When the value of a parameter for the remaining travel in--range
signal is 0.
NOTE
1 The DEN2 signal remains 0 during jog feed (JOG).
2 The DEN2 signal maintains its current state until another
move command is issued.
(2) Distribution pulse signal IPLX
[Classification]
Input signal <Xx+0#1> (common to both the peripheral equipment
control and direct command interfaces)
[Function]
This signal indicates that the servo amplifier unit has axis move
command distribution pulses that have not been used for axis
movement (residual movement amount).
[Input condition]
The signal is 1 when:
1. There are axis move command distribution pulses that have not
been used for axis movement (residual movement amount).
The signal is 0 when:
1. There is no axis move command distribution pulse that has not
been used for axis movement (residual movement amount).
NOTE
The IPLX signal is valid while jog feed (JOG) mode is set.
2.3.6
Status Signals