3. INPUT AND OUTPUT OF DATA
B63175EN/03
256
Parameters can be input and output using the ALL IO screen.
Inputting parameters
1 Press soft key [PARAM] on the ALL IO screen, described in Section
3.3.1.
2 Select EDIT mode.
3 Press soft key
[(OPRT)]. Soft keys change as shown below.
READ PUNCH
4 Press soft key [READ], then [EXEC].
The parameters are read, and the INPUT indicator blinks at the
lowerright corner of the screen. Upon the completion of input, the
INPUT indicator is cleared from the screen.
To cancel input, press soft key
[CAN].
Outputting parameters
1 Press soft key [PARAM] on the ALL IO screen, described in Section
3.3.1.
2 Select EDIT mode.
3 Press soft key
[(OPRT)]. Soft keys change as shown below.
READ PUNCH
4 Press soft key [PUNCH], then [EXEC].
The parameters are output, and the OUTPUT indicator blinks at the
lowerright corner of the screen. Upon the completion of output, the
OUTPUT indicator is cleared from the screen.
To cancel output, press soft key
[CAN].
3.3.3
Inputting and
Outputting Parameters
Procedure
EXECCAN
Procedure
EXECCAN