Fanuc Power Mate i-D/H Operation Maintenance Handbook

6. STATUS DISPLAY BY SELFDIAGNOSTIC DISPLAY
115
No. #7
#6 #5 #4 #3 #2 #1 #0
311
DUA XBZ GSG AL4 AL3 AL2 AL1
#0(AL1) : An APC alarm was issued.
#2(AL3) : The detected APC battery voltage is 0 V (serial pulse coder).
#3(AL4) : An abnormal rotation speed (RCAL) was detected.
#4(GSG): The G202 signal was brought from 0 to 1.
#1(AL2) : A disconnection was detected.
#6(DUA) : While the dual position feedback function was being used, the
difference in error between the semiclosed loop side and the
closed loop side became too large.
#5(XBZ) : The detected APC battery voltage is 0 V (serial separate position
detector).
6.1.10 Spindle data (No. 400–420)
No.
#7
#6 #5 #4 #3 #2 #1 #0
400
SAI SSR POS SIC
SIC 0: The module required for spindle serial control is not installed.
1: The module required for spindle serial control is installed.
POS 0: The module required for spindle analog control is not installed.
1: The module required for spindle analog control is installed.
SSR 0: Spindle serial control is not used.
1: Spindle serial control is used.
SAI 1: Spindle analog control is not used.
0: Spindle analog control is used.
No.
401
Serial spindle alarm state of spindle
Information related to communication errors in the spindle serial output
interface
No.
#7
#6 #5 #4 #3 #2 #1 #0
408
SSA SCA CME CER SNE FRE CRE
CRE 1: A CRC error occurred (warning).
FRE 1: A framing error occurred (warning).
SNE 1: The sender/receiver is incorrect.
CER 1: A receiver error occurred.
CME 1: In automatic scanning, no response is returned.
SCA 1: A communication alarm is issued on the spindle amplifier side.
SSA 1: A system alarm is issued on the spindle amplifier side.
(These states represent the causes of spindle alarm No. 749. These states
are caused mainly by noise, disconnection, and momentary power failure.)