9.1.11 List of alarms (PMC)
(1) Alarm messages (PMC)
Message Contents and solution
ALARM NOTHING Normal status
ER01 PROGRAM
DATA ERROR (RAM)
The sequence program is defective.
Please clear the RAM and input LADDER again.
ER02 PROGRAM
SIZE OVER
The size of sequence program exceeds the maximum
size of LADDER.
Please change MAX LADDER AREA SIZE at the
SYSPRM screen and restart the system.
ER03 PROGRAM
SIZE ERROR
(OPTION)
The size of sequence program exceeds the option speci-
fication size.
Please increase the option specification size.
Or, reduce the size of sequence program.
ER04 PMC TYPE
UNMATCH
The PMC model setting of the sequence program is not
corresponding to an actual model.
Re–convert the machine model, using an offline program-
mer.
ER05 PMC MODULE
TYPE ERROR
The module type of the PMC engine is not correct.
Please change the base PC board.
ER07 NO OPTION
(LADDER STEP)
There is no step number option of LADDER.
ER10 OPTION AREA
NOTHING
(series name)
The management software for the PMCSB has not been
transferred.
The software installation is not consistent with the order.
Contact FANUC.
ER12 OPTION AREA
ERROR
(series name)
The series of the management software for the PMC–SB
differs between BASIC and OPTION.
Contact FANUC.
ER14 OPTION AREA
VERSIION ERROR
(series name)
The edition of the management software for the PMC–SB
differs between BASIC and OPTION.
Contact FANUC.
ER17 PROGRAM
PARITY
The parity error occurred on FROM for sequence program
or the RAM.
ROM: The deterioration of FROM may be deteriorated
Please exchange memory module.
ER18 PROGRAM
DATA ERROR BY I/O
Transferring the sequence program from offline program-
mer was interrupted by the power off etc.
Please clear the sequence program and transfer the se-
quence program again.
ER19 LADDER DATA
ERROR
Editing the LADDER was interrupted by the power off or
by the switch to the CNC screen by the function key etc.
Please edit LADDER once on PMC.
Or, please input LADDER again.
ER20 SYMBOL/
COMMENT DATA
ERROR
Editing the symbol and comment was interrupted by the
power off or by the switch to the CNC screen by the func-
tion key etc.
Please edit symbol and comment once on PMC.
Or, please input symbol and comment again.