Fanuc Power Mate i-D/H Operation Maintenance Handbook

10. PMC
351
10.3 PMC Parameter
10.3.1 Input of PMC parameter from MDI
1 Select MDI mode or depress EMERGENCY STOP button.
2 [PWE] set to “1” on SETTING screen or PROGRAM PROTECT
signal (KEY4) turn to “1”.
PWE KEY4
f
f
f
f
f either one
Timer
Counter
Keep relay
Data table
f
either one
3 Select the display screen by soft key.
[TIMER] : Timer screen
[COUNTER] : Counter screen
[KEEPRL] : Keep relay screen
[DATA] : Data table screen
4 Move the cursor to desired number.
5 Input the Numeral
and press
INPUT
key then the data
inputted.
6 [PWE] on SETTING screen or [KEY4] return to “0” after data set.
10.3.2 Timer screen (TIMER)
The variable timer (SUB 3) time is set.
TIMER
[][ ][][][]
COUNTR KEEPRL DATA SETING
PMC PARAMETER (TIMER) #001
NO. ADDRESS DATA NO. ADDRESS DATA
01 T00 480 11 T20 0
02 T02 960 12 T22 0
03 T04 0 13 T24 0
04 T06 0 14 T26 0
05 T08 0 15 T28 0
06 T10 0 16 T30 0
07 T12 0 17 T32 0
08 T14 0 18 T34 0
09 T16 0 19 T36 0
10 T18 0 20 T38 0
MONIT RUN
Setting
time by
msec unit
Refer the address by ladder
program
Specified timer number by program
Page number (change by page cursor key)
Setting time : Timer No. 1 8 =Max.=1572.8 sec, each 48msec.
Up to 262.1 seconds in units of 8 ms for timer Nos.
9 to 40 subsequent timers (timer Nos. 9 to 150 in
the SB6)