Fanuc Power Mate i-D/H Operation Maintenance Handbook

10. PMC
353
ii) PMC system parameter
Since the system uses keep relays K17 to K19 (K900 to K902 for the
SB6), they cannot be used by a sequence program.
K17
or
K900
#7 #6 #5 #4 #3 #2 #1 #0
DTBLDSP ANASTAT TRCSTART MEMINP AUTORUN PRGRAM LADMASK
#7 (DTBLDSP) 0 : The PMC parameter data table control screen is
displayed.
1 : The PMC parameter data table control screen is
not displayed.
#6 (ANASTAT) 0 : Pressing the soft key to execution starts sampling
by the signal waveform display function.
1 : The signal waveform display function
automatically starts sampling at power on.
: This bit is only effective for those models for which the signal
waveform display function is applicable.
#5 (TRCSTAT) 0 : Pressing the [EXEC] soft key starts tracing by the
signal trace function.
1 : The signal trace function automatically starts
tracing at power on.
#4 (MEMINP) 0 : Data cannot be input by using the memory
contents display function.
1 : Data can be input by using the memory contents
display function.
#2 (AUTORUN) 0 : The sequence program automatically starts at
power on.
1 : Pressing the soft key to sequence program
execution starts the sequence program.
#1 (PRGRAM) 0 : The built-in programmer function does not
operate. (Also, the programmer menu is not
displayed.)
1 : The built-in programmer function operates. (The
programmer menu is displayed.)
#0 (LADMASK) 0 : The ladder programs are displayed dynamically
(PMCLAD).
1 : The ladder programs are not displayed
dynamically (PMCLAD).