Fanuc Power Mate i-D/H Operator Manual

G. ALARM LIST
B–63174EN/03
APPENDIX
604
8) Serial pulse coder (SPC) alarms
When either of the following alarms is issued, a possible cause is a faulty serial pulse coder or cable.
Number Message Contents
360 n AXIS : ABNORMAL CHECKSUM (INT) A checksum error occurred in the built–in pulse coder.
361 n AXIS : ABNORMAL PHASE DATA
(INT)
A phase data error occurred in the built–in pulse coder.
362 n AXIS : ABNORMAL REV.DATA (INT) A rotation speed count error occurred in the built–in pulse coder.
363 n AXIS : ABNORMAL CLOCK (INT) A clock error occurred in the built–in pulse coder.
364 n AXIS : SOFT PHASE ALARM (INT) The digital servo software detected invalid data in the built–in pulse
coder.
365 n AXIS : BROKEN LED (INT) An LED error occurred in the built–in pulse coder.
366 n AXIS : PULSE MISS (INT) A feedback error occurred in the built–in pulse coder.
367 n AXIS : COUNT MISS (INT) A count error occurred in the built–in pulse coder.
368 n AXIS : SERIAL DATA ERROR (INT) Communication data from the built–in pulse coder cannot be re-
ceived.
369 n AXIS : DATA TRANS. ERROR (INT) A CRC or stop bit error occurred in the communication data being
received from the built–in pulse coder.
380 n AXIS : BROKEN LED (EXT) The separate detector is erroneous.
381 n AXIS : ABNORMAL PHASE (EXT LIN) A phase data error occurred in the separate linear scale.
382 n AXIS : COUNT MISS (EXT) A pulse error occurred in the separate detector.
383 n AXIS : PULSE MISS (EXT) A count error occurred in the separate detector.
384 n AXIS : SOFT PHASE ALARM (EXT) The digital servo software detected invalid data in the separate de-
tector.
385 n AXIS : SERIAL DATA ERROR (EXT) Communication data from the separate detector cannot be received.
386 n AXIS : DATA TRANS. ERROR (EXT) A CRC or stop bit error occurred in the communication data being
received from the separate detector.
The details of serial pulse coder alarm No. 350 (pulse coder alarm) are
displayed in the diagnosis display (No. 202) as shown below.
#7
202
#6
CSA
#5
BLA
#4
PHA
#3
RCA
#2
BZA
#1
CKA
#0
SPH
SPH : The serial pulse coder or feedback cable is defective. Replace the serial
pulse coder or cable.
CKA : The serial pulse coder is defective. Replace it.
BZA : The pulse coder was supplied with power for the first time.
Make sure that the batteries are connected.
Turn the power off, then turn it on again and perform a reference position
return. This alarm has nothing to do with alarm No. 350 (serial pulse coder
alarm).
RCA : The serial pulse coder is defective. Replace it.
PHA : The serial pulse coder or feedback cable is defective. replace the serial
pulse coder or cable.
BLA : The battery voltage is low. Replace the batteries. This alarm has nothing
to do with alarm No. 350 (serial pulse coder alarm).
CSA : The serial pulse coder is defective. Replace it.
The details of serial
pulse coder alarm
No.350