8. CONNECTION TO SETTING AND DISPLAY UNIT
B63173EN/03
290
2) Connection panel
The connection panel can be used to make the handy operators panel
detachable from the cabinet.
On the connection panel, install a connector to which the handy
operators panel cable can be attached, and also install a switch to
enable/disable the handy operators panel.
To connector
panel relay
DIS
CONNECT
Handy operators panel enable switch
A switch with contact A and contact B is required. contact A is used
to feed 24 VDC to the handy operators panel, while contact B is
used for bypassing handy operators panel emergency stop while the
switch is set to DISCONNECT.
Example of switch
CONNECT
Handy operators
panel
Handy operators panel
enable switch
Connector panel
SR1
Connection panel
Emergency stop
24 VDC input
24V
(1)While the enable switch is set to DISCONNECT (while the switch is
off)
D The handy operators panel does not receive 24 VDC, hence cannot
be used.
D Emergency stop cannot be performed from the handy operators
panel.
(2)While the enable switch is set to CONNECT (while the switch is on)
D The handy operators panel receives 24 VDC, hence can be used.
D Emergency stop can be performed from the handy operators panel.
The emergency stop described above occurs when the emergency stop
button on the handy operators panel is pressed, or when the deadmans
switch enable switch is on and both of the deadmans switches are
released.