FANUC Power Mate i-MODEL H CONNECTION MANUAL (HARDWARE)

Edit.
DATE Design
Description
DRAW.NO.
B-63173EN/03-2
CUST.
TITLE
SHEET
3 / 7
AC input
α
i
PS
24V power
supply
System ground (PE)
α
i
SP
α
i
SV
CX1A
Grounded near
each device.
JF*
Cabinet
(Sheet metal with low impedance)
Machine side
Signal
line
Power
line
Wire the signal line away
from the power line.
CNC
O
p
erator’s
p
anel
Pendant box
(Sheet metal with low impedance)
G
r
ound bar for the
shield clamping
Connect at
low impedance.
Fig. 1 Multi-point grounding method
Note: The connection surface of the grounding
line should not be painted.
Frame ground
System ground (PE)