B63180EN/02
4. DESCRIPTION OF PARAMETERS
177
DSL If the selection of an axis is changed when PMC axis selection is disabled:
0 : P/S alarm No.139 is issued.
1 : The change is valid, and no alarm is issued for an unspecified system.
NCI In axis control by the PMC, a position check at the time of deceleration is:
0 : Performed.
1 : Not performed.
NOTE
Bit 0 (CMV), bit 1 (NMT), and bit 5 (DSL) of this parameter
is valid when bit 7 (EA2) of parameter No. 8003 is set to 0.
#7
8005
#6 #5 #4 #3
DRR
#2
R10
#1 #0
[Data type] Bit
R10 When the RPD parameter (bit 0 of parameter No.8002) is set to 1, the unit
for specifying a rapid traverse rate for the PMC axis is:
0 : 1 mm/min.
1 : 10 mm/min.
DRR For cutting feed per rotation in PMC axis control, the dry run function is:
0 : Disabled.
1 : Enabled.
NOTE
Bit 2 (R10) and bit 3 (DRR) of this parameter is valid when
bit 7 (EA2) of parameter No. 8003 is set to 0.
#7
8006
#6 #5 #4 #3
EDL
#2 #1 #0
[Data type] Bit
EDL For PMC axis control, axis directionspecific interlock is:
0 : Disabled.
1 : Enabled.
NOTE
This parameter is valid when bit 7 (EA2) of parameter No.
8003 is set to 0.