4. DESCRIPTION OF PARAMETERS
17
If the station of interest is #1 and is to receive DO data from slave stations
#2 and #3, specify 3.
If the station of interest is #2 and is to receive DO data from slave stations
#1 and #3, specify 3.
If the station of interest is #3 and is to receive DO data from slave stations
#1 and #2, specify 3.
If the station of interest is #3 and to receive DO data from slave stations
#1, #2, and #4, specify 4.
0181 Internal relay address for the beginning of input data
[Data type] Word
[Valid data range] 0 to 999
This parameter is used if the global I/O transfer function is used.
Set the R address for acquiring input data.
0182 Internal relay address for the beginning of output data
[Data type] Word
[Valid data range] 0 to 999
This parameter is used if the global I/O transfer function is used.
Set the R address for acquiring output data.
0187 Internal relay address for the beginning of communication status data
[Data type] Word
[Valid data range] 0 to 999
Set the R address for the status data to be sent.
A 32byte area (for 32 stations) is unconditionally acquired from the
specified R area.
0188 Communication timeout
[Data type] Word
[Unit of data] ms
[Valid data range] 1 to 1000
Set a communication timeout value. If you specify 0, a default value
(300 ms) is used.
NOTE
Refer to FANUC I/O LinkII Connection Manual
(B62714EN) for detailed descriptions about the I/O LinkII
function.