Function of interception of the power line to motor at Alpha(HV)i series SVM
1. Overview
So far the external MCC has been necessary to cut the power to motor of the each axis.
The power to the motor can be cut by this function instead of connecting external MCC.
2. Applied SVM
(1) SVM1-10HVi: A06B-6124-H102
(2) SVM1-20HVi: A06B-6124-H103
(3) SVM1-40HVi: A06B-6124-H104
(4) SVM1-80HVi: A06B-6124-H105
3. Circuit and Block diagram
(1) Block diagram
Driver for the
power transisitor
Power transistors
PWM signals
0V
5V
24V
Motor
0V
External
contact
Contact
B
Contact
A
Relay
K50
SVM
CN7-A3
-
CN7-A2
CN7-
1
Monitor
(2) Function
1) The safety relay “K50” operates by external contact signal.”
2) The contact “A” (a contact) of the relay “K50” cuts off the power supply of the driver for
the power transistor.
3) The contact “B” (b contact) of the relay “K50 is used to monitor the status.
(3) Operation of the circuit
When the external contact closes, the contact “A” of the relay “K50” closes. The power
supply of the driver for power transistors turns on, then input for the power transistors are
enabled. The contact “B” is open in this state.
When the external contact is open, the contact “A” cuts off the power supply of the driver
for power transistor, and the power transistors turn off forcedly. The contact “B” closes in
this state.
TITLE
DRAW.
No.
1 / 3
Page
FANUC LTD
DESCRIPTION DESIGN DATE
EDIT
Cut off the power line to motor
at Alpha(HV)i series SVM
A-72562EN-0025
1