2. Parameters
#7 #6 #5 #4 #3 #2 #1 #0
3106 OHS OHP
[Data type] Bit
OHP The operation history screen is :
0 : Not displayed.
1 : Displayed.
OHS Operation history sampling is :
0 : Performed.
1 : Not performed.
#7 #6 #5 #4 #3 #2 #1 #0
3112 OPH
[Data type] Bit
OPH The operation history function is
0 : Enabled.
1 : Disabled.
Note
When this parameter is set, the power must be turned off before operation
is continued.
3122 Time interval used to record data in the operation history
[Data type] Word
[Unit of data] min
[Valid data range] 0 to 1439
Time data is recorded in the operation history at set intervals. When 0 is specified in
this parameter, 10 minutes is assumed as the default.
However, note that time data is not recorded if there is no data to be recorded at the
specified time.
Edit
Apprv.
Desig.
Sheet
TITLE
Draw
No.
Date
Design
Descri
tion
Date
FANUC Series 16i/18i/21i–A/B
Expansion of the setting range of signals on
o
eration histor
S
ecifications
A-90015E
2002.7.31
3
7