3. START-UP PROCEDURE
B–65195EN/01
START-UP PROCEDURE
20
4. Specify the motor ID No.
Select the motor ID No. according to the model and specification
(four digits in the middle segment of A06B–XXXX–BXXX) of
your motor.
Motor model α12HV α22HV α30HV αC3/2000 αC6/2000 αC12/2000 αC22/1500
Motor specification 0176 0177 0178 0142 0123 0127 0128
Motor type No. 3 4 5 7 8 9 10
α0.5 α3/3000 α6/2000 α6/3000 α12/2000 α12/3000 α22/2000 α22/3000
0142 0123 0127 0128 0142 0143 0147 0148
13 15 16 17 18 19 20 21
α30/2000 α30/3000 αM3/3000 αM6/3000 αM9/3000
0152 0153 0161 0162 0163
22 23 24 25 26
α22/1500 α30/1200
α40/2000
with FAN
α40/2000
without FAN
E6/2000 E1/3000 E2/3000
0146 0151 0158 0157 0106 0101 0102
27 28 29 30 34 35 36
α2/2000 αL3/2000 αL6/3000 αL9/3000 αL25/3000 αL50/2000 α1/3000 α2/3000
0372 0561 0562 0564 0571 0572 0371 0373
46 56 57 58 59 60 61 62
5. Set AMR as described below. The setting does not depend on the
model of the motor.
α pulse coder 00000000
6. Set CMR with the scale of a distance the NC instructs the
machine to move.
CMR = Command unit/Detection unit
CMR 1/2 to 48 Setting value = CMR 2
Usually, CMR=1, so specity 2.
7. Specify the flexible feed gear (F.FG). This function makes it easy
to specify a detection unit for the leads and gear reduction ratios
of various ball screws by changing the number of position
feedback pulses from the pulse coder and separate detector.
1000000
Number of position pulses neces-
sary for each revolution of the motor
Setting for the α pulse coder and serial pulse coder A in the semi–closed mode
=
(Note1)
F.FG numerator (32767)
F.FG denominator (32767)
(as irreducible fraction)
NOTE1
For both F.FG numerator and denominator, the maximum
setting value (after reduced) is 32767.