FANUC Series 16i/160i –L
Automatic leak check function
Specifications
A-78037E
00.03.17
K.Suzuki
Contents
Date
Design
M.Sato
Title
of
Drawing
Drawing
No
Page
3. Parameters
#7 #6 #5 #4 #3 #2 #1 #0
15153 LCK
Data type : Bit type
LCK 0 : Automatic leak check function is disabled.
1 : Automatic leak check function is enabled
15154 Leak judgement time
Data type : Word type
Data unit : Second
Data range : 3 - 65535
The time for keeping laser gas pressure with all valves closing should be set.
Laser gas pressure is logged for 4 times while the set time.
Automatic leak check function does not work if the value from 0 to 2 is set.
15256 Evacuating time in RUN-OFF sequence
Data type : Word type
Data unit : Second
Data range : 0 – 32767 (standard setting 600)
If gas pressure control start signal (G222#6:RUN) is turned off with setting
PRM.15003#2 to ‘1’, oscillator is evacuated for the set time.
This parameter exists before addition of this function.
However, the minimum setting value is changed from 600 to 0.
4. External signals
#7 #6 #5 #4 #3 #2 #1 #0
G224 LCKON
I/O division : Input
LCKON 0 : Automatic leak check function is disabled.
1 : Automatic leak check function is enabled
#7 #6 #5 #4 #3 #2 #1 #0
F224 AVCL LCKMD
I/O division : Output
LCKMD 0 : Normal sequence
1 : Leak check mode
AVCL 0 : Normal state
1 : State that all valve shut