1.DeviceNet FUNCTIONS SETTING B-64044EN/01
- 14 -
Setting item
Item Description
NETWORK Sets whether the DeviceNet master is removed from
or added to the network.
OFFLINE : Removed from the network.
ONLINE : Added to the network.
BAUDRATE Sets the communication rate.
The communication rate is limited by the maximum
length or maximum total branch length of a network.
For details, see Section 1.1 "CABLE LENGTH AND
TRANSFER RATE" in Part III "CONNECTION."
One of 125 Kbps, 250 Kbps, and 500 Kbps can be
set.
DI DATA ON
ABNORMAL
Sets whether DI data is restored to the value before
occurrence of a communication error or cleared to 0
when communication stops due to a communication
error.
HOLD: DI data is restored to the value before
occurrence of a communication error.
CLEAR: DI data is cleared to 0.
MAC ID (0 - 63) Sets the MAC ID of the DeviceNet master.
The MAC ID must be unique on the network.
The setting range is between 0 and 63.
COMMON
STATUS
ADDRESS
Sets the address of the PMC area in which the
common status is to be stored. When the common
status is not required, set a space (SP).
The setting range is the R or E area of PMC.
COMMON
STATUS SIZE
Sets the size of the PMC area in which the common
status is to be stored. When the common status is
not required, set 0.
The setting range is 0, 2, 4, and 6 to 14.
CYCLE TIME
(SETTING)
Sets the communication cycle time.
0: Highest value
1 to 500 : 1 ms to 500 ms
Display item
Item Description
CYCLE TIME
(CURRENT)
The current value of the communication cycle time is
displayed.
CYCLE TIME
(MAXIMUM)
The maximum value of the communication cycle time
is displayed.
CYCLE TIME
(MINIMUM)
The minimum value of the communication cycle time
is displayed.