A-72937EN/11
To meet the requirement of the EMC Directive
TMN06007E_A-72937EN_11.DOC
- 16 -
One of the suitable absorbers is available from Okaya Electric Industries. The
type number is as follows.
200V system
for between lines
R・A・V-781BYZ-2 (Okaya Electric)
for between line and earth
R・A・V-781BXZ-4 (Okaya Electric)
200V system (united type)
for between lines &
for between line and earth
R・C・M-601BUZ-4 (Okaya Electric)
400V system
for between lines
R・A・V-152BYZ-2A (Okaya Electric)
for between line and earth
R・A・V-801BXZ-4 (Okaya Electric)
3.4 Spark killers
Be sure to provide spark killers to all the inductive equipment. FANUC
recommends CR network for AC circuit and diodes for DC circuit. Varistors
just cut the peak voltage and the steep rising edge of voltage remains as it is,
so it is not recommended.
3.5 Grounding of equipment
All the equipments should be grounded as the vendors recommend regardless
to the location the equipments are installed (inside/ outside of the cabinet).