5.TOTAL CONNECTION DIAGRAMA-72562EN-027
- 23 -
5.3.1.3 Details of cable K7
Cable K7 is used to supply an emergency stop signal to the SVPM.
Emergency stop
contact
Connector tyco Electronics AMP
D-3200 series
Hausing 1-178128-3 (1 pcs.)
Contact 1-175218-2 (2 pcs.)
(Ordering numbef : A06B-6134-K201)
Cable Two-conductor polyvinyl heavy-duty power cable (JIS
C3312)
Conductor size 1.25 mm
2
(50/0.18)
PVC sheath 9.6 mm in diameter
(1) When the contact is ON (closed), the spindle motor and servo motor are enabled.
When the contact is OFF (open), the external magnetic contactor (MCC) is in the
off state, and the spindle motor and servo motor do not operate.
(2) When the contact is set to OFF (open) during motor rotation, the spindle motor
decelerates, then stops, and the servo motor is stopped by the dynamic brake.
(3) The contact input signal is specified as follows:
<1> As the external contact capacity, a voltage of at least 30 VDC and a current
of at least 100 mA are required.
<2> Significant levels (with the voltage between input pins) when the contactless
signal input mode is used:
Low level "logic 0": Up to 2 V
High level "logic 1": At least 20 V
(4) There is necessity to open the contact signal (CX4:ESP) within 200(ms) from the
break of main power of SVPM when main power turns off at condition that the
safty door opens.The alarm (DC link low voltage alarm) occures when main
power of SVPMturns off with the contact signal (CX4:ESP) opened