G.MEMORY CLEAR APPENDIX B-63945EN/02
- 766 -
G.1 OVERVIEW
If an unexpected error occurs, such as the "SYSTEM LABEL CHECK
ERROR" at system startup or the "SYSTEM ALARM", which may be
generated suddenly, this function can start up the CNC system in its
initial state to return the system to the state in which restoration work
can be performed, by clearing all data stored in CNC memory.
G.2 OPERATION METHOD
1. Starting method
<1> For FS30
i
-A
When turning the power ON to the CNC, turn the power ON
while pressing the MID keys
RESET
and
DELET
at the same time
and holding them down. Keep holding them down until the
memory all clear approval screen is displayed.
<2> For FS300i-A/ FS300is-A
Use the NC BOOT32 function to display the IPL menu.
From the IPL menu, select "2. BACK-UP CNC DATA ALL
CLEAR".
For details, see the chapter on "Maintenance Operations (Boot
and IPL) for Open CNC".