2.5 Feed rates
There is danger that an actual feed rate of the slave axis grows more remarkably than usually during
overlapping control because the distribution pulse from the master axis is added to own distribution
pulse. ("usually" indicates rapid traverse rate etc. to which the parameter is set.) It is necessary to set
the feed rate used only during overlapping control to prevent this. The feed rate and the time constant
used only during overlapping control are as follows.
!
Rapid traverse rate parameter No.8190
!
F0 feed rate of rapid traverse override parameter No.8191
!
Time constant of liner acceleration/deceleration of rapid traverse parameter No.8192
!
Maximum cutting feed rate parameter No.8193
Manual rapid traverse feed rate one with small parameter No.8190 and No.1424
Both master axes and slave axes use these parameters which are particularly set during overlapping
control. An appropriate value is set in consideration of the feed rate after the pulse is added. The
maximum cutting feed rate is not changed during two blocks including the current block when
overlapping control is switched in automatic operation. However, the maximum cutting feed rate is
changed when the next block is executed in case of none-buffering M-code is commanded. Feed rates
except the maximum cutting feed rate are changed as soon as the overlapping control is begun or is
released.
2.6 Differences between normal synchronous control and overlapping control
The synchronous error correction and the synchronous error detection are not performed
between the master axis and the slave axis of the overlapping control.
The parking signal is invalid to the axis controlling overlapping.
When the overlapping control is released in automatic operation, movement command and
coordinate system setting can be commanded at once to the overlapping slave axis. There is
no limit that movement command is prohibited in 2 or 3 blocks like the synchronous control.
The reference point return cannot be commanded in the overlapping slave axis.

Contents Summary of One Path Overlapping Control Additional Manual

  • Page 1FANUC Series 16Ii/ 18i -TA/TB One Path Overlapping control on two paths system Specifications 1. Overview .............................................2 2. Details..................................................2 3. Parameters..........................................4 4. Signals .................
  • Page 21. Overview This function enables one path overlapping control on two paths system. 2. Details 2.1 Overlapping control Overlapping control function add the distribution pulse of an axis (overlapping master axis) to the distribution pulse of another axis (overlapping slave axis). It looks like the sy
  • Page 32.5 Feed rates There is danger that an actual feed rate of the slave axis grows more remarkably than usually during overlapping control because the distribution pulse from the master axis is added to own distribution pulse. ("usually" indicates rapid traverse rate etc. to which the parameter is set.
  • Page 43. Parameters #7#6#5#4#3#2#1#0 8160 NRS SIC Data format : Bit type NRS : When RESET is executed, overlapping control is  0 : Cancelled. 1 : Not cancelled. #7#6#5#4#3#2#1#0 8162 OMPx Data format : Bit type OMPx : When mirror image is effective, the sign of o
  • Page 58186 Overlapping master axis of each axis Data format : Byte axis type Data range: 1,2,3,...,Number of controlled axis,(11,12,13,…,10+Axis number) 21,22,23,…..,20+Axis number The axis index of the master axis which overlaps of each axis is set. The axis, to which 0 is set, does not become overlappi
  • Page 68190 Rapid traverse rate of each axis during overlapping control Data format : 2 words axis type Data unit : Data range: Data range Increment system Data unit IS-A, IS-B  IS-C Metric system machine  1 mm/min 30 240000 30 100000 Inch system machine 0.1 inch/min 30 96000 30 48000 Rotar
  • Page 78191 Rapid traverse override F0 rate of each axis during overlapping control Data format : words axis type Data unit : Data range: Data range Increment system Data unit IS-A, IS-B  IS-C Metric system machine  1 mm/min 6 15000 6 12000 Inch system machine 0.1 inch/min 6 6000 6 4800 
  • Page 84. Signals #7 #6 #5 #4 #3 #2 #1 #0 G0190/G1190 OVLS8 OVLS7 OVLS6 OVLS5 OVLS4 OVLS3 OVLS2 OVLS1 Overlapping control selection signal (input) To turn this signal to HIGH from LOW starts overlapping control of corresponding axis. The axis set in parameter No.8186 is made the master axis. However, when
  • Page 95. Remarks 5.1 Remarks of overlapping controls 1 The controlled axis must stop at beginning or releasing overlapping control. 2 Two or more axes can be put into the state of overlapping control at the same time. But it is impossible to overlap an axis with multiple axes at the same time. 3 Least com
  • Page 10Mirror image It is invalid to the overlapping pulse. (1) Machine lock It is invalid to the overlapping pulse. (1) Interlock It is invalid to the overlapping pulse. (1) Skip function Available. Automatic tool offset The overlapping slave axis is impossible. Tool setter The overlapping slave axis is i
  • Page 115.4 Releasing of overlapping control The overlapping control are released for the following besides the overlapping control selection signal is turned off. (1) Emergency stop (2) Reset (3) Servo alarm (4) Servo off (5) Over travel alarm (6) Alarm concerning overlapping control (7) P/S000 alarm When
  • Page 126. Alarm When the following alarms are issued, overlapping control of all axes will be released. Number Content 225 This alarm is issued in the following cases.(When overlapping control command are released, it is detected) (1) When mistake is found in setting parameter of the axis index. (2) When m