4 - 12 Alpha Series servo Amplifier Module (SVM) with FSSB - April 1998 GFK-1546
4
Parameter No. 1936 – 1937
No.
1936 Connector number for the first pulse module
1937 Connector number for the second pulse module
Data Type: Byte Axis
Data Range: 0 - 7
For a pulse module, set a value which is one less than the connector number for each axis. Use
zero (0) for an axis where the pulse module is not used.
You can use any combination of axis and connector, but you must use the lowest available
number. For example, you cannot use Connector No. 3 without using No. 2.
Example:
Axis
1st Module
Connector No.
2nd Module
Connector No.
No. 1936 No. 1937
No. 1905
(#7, #6)
X 1 not used 0 0 0, 1
Y not used 2 0 1 1, 0
Z not used 1 0 0 1, 0
A not used not used 0 0 0, 0
B 2 not used 1 0 0, 1
C not used 3 0 2 1, 0
Note
When parameter No. 1902#0=0, these bits are set automatically. When
parameter No. 1902#0=1, these bits must be set manually.