7. TROUBLESHOOTING
B–63665EN/01
262
3) Interlock signal per axis and direction (+/– MITn) is input
#7
G0132
#6 #5 #4 #3
+MIT4
#2
+MIT3
#1
+MIT2
#0
+MIT1
G0134 –MIT4 –MIT3 –MIT2 –MIT1
Check the signals using PMC’s diagnostic function (PMCDGN)
#7
*JV7G0010
#6
*JV6
#5
*JV5
#4
*JV4
#3
*JV3
#2
*JV2
#1
*JV1
#0
*JV0
*JV15G0011 *JV14 *JV13 *JV12 *JV11 *JV10 *JV9 *JV8
When the override is 0% all bits of the above address becomes
1111 1111 or 0000 0000.. . . . . . . . . .
*JV15 JV0. . . . . . . . . . Override
1111 1111 1111 1111
1111 1111 1111 1110
:
1101 1000 1110 1111
:
0000 0000 0000 0001
0000 0000 0000 0000
0.00%
0.01%
:
100.00%
:
655.34%
0.00%
In this case, RESET is also displayed on the status display. Check it using
the procedure of 1 above.
(4)Jog feed rate setting (Parameter) is not correct.
1423 Jog feedrate per axis
c. Jog feedrate override is
0%
d.NC is in a reset state