B–63833EN/03
3. INSTALLATION
10
The peripheral units and the control unit have been designed on the
assumption that they are housed in closed cabinets. In this manual
“cabinet” refers to the following:
D Cabinet manufactured by the machine tool builder for housing the
control unit or peripheral units;
D Operation pendant, manufactured by the machine tool builder, for
housing the control unit or operator’s panel.
D Equivalent to the above.
The environmental conditions when installing these cabinets shall
conform to the following table. Section 3.3 describes the installation and
design conditions of a cabinet satisfying these conditions.
Ambient
Operating 0°C to 55°C
Temperature
Storage, Transport –20°C to 60°C
Normal 75%RH or less, no condensation
Humidity
Short period
(less than 1 month)
95%RH or less, no condensation
Operating 0.5 G or less
Vibration
Non–operating 1.0 G or less
Meters above
Operating Up to 1000 m
sea level
Non–operating Up to 12000 m
Environment
Normal machine shop environment
(The environment must be considered if the cabinets are in
a location where the density of dust, coolant, and/or organic
solvent is relatively high.)
3.1
ENVIRONMENT FOR
INSTALLATION
3.1.1
Environmental
Requirements Outside
the Control Unit