B--63005EN/02
1. DISPLAY AND OPERATION
67
Detail
number
MeasureCause
Parameter
number
0843 2084 No positive value has been set for the
flexible feed gear numerator.
Alternatively, the following condition ex-
ists: Feed gear numerator > denominator
Specify a positive value as the flexible
feed gear numerator.
Alternatively, satisfy the following condi-
tion: Feed gear numerator ≦ denomina-
tor (except for phase A--/B --specific
stand--alone type detector).
0853 2085 No positive value has been set as the
flexible feed gear denominator.
Specify a positive value as the flexible
feed gear denominator.
0884
0885
0886
2088 The internal value of the machine velocity
feedback coefficient has overflowed.
Decrease the machine velocity feedback
coefficient.
Alternatively, use the damping control
function, which has an equivalent effect.
0883 2088 A value of 100 or greater was specified in
the machine velocity feedback coefficient
for an axis with a serial s tand--alone type
detector.
The maximum allowable value for the ma-
chine velocity feedback coefficient for
axes with a serial stand --alone type detec-
tor is 100. Decrease the setting to within
100.
0926
0927
0928
2092 The interval value of the advance feedfor-
ward coefficient has overflowed.
Use the position gain magnification func-
tion.
0996 2099 The internal value for suppressing N
pulses has overflowed.
Decrease the setting of the parameter
listed at the left.
1123 2112 No value has been entered for the AMR
conversion coefficient parameter when a
linear motor is in use.
Specify the AMR conversion coefficient.
1183 2118 No value has been specified in the semi--/
full--closed loop error threshold parameter
for a full--closed loop linear motor (for the
Series 9080 only).
Specify a semi--/full--closed loop error
threshold value for the parameter listed at
the left.
1284
1285
2128 If the value specified as the number of ve-
locity pulses is small, the internal value of
the current control parameter overflows.
Decrease the value for the parameter
listed at the left to within a range where no
alarm will occur any longer.
1294
1295
2129 If the value specified as the number of ve-
locity pulses is large, the internal value of
the current control parameter overflows.
Re--set “a” to a smalle r value when the
setting of the parameter lis ted at the left is
broken up into: a ⌠ 256 + b
1393 2139 The setting of the linear motor AMR offset
has exceeded 45.
Decrease the setting of the parameter
listed at the left to within 45.
1446
1447
1448
2144 The cutting feedforward coefficient for the
cutting--/rapid traverse--specific FAD func-
tion has overflowed.
Use the position gain magnification func-
tion.
1454
1455
1456
1459
2145 The cutting velocity feedforward coeffi-
cient for the cutting --/rapid traverse--spe-
cific FAD function has overflowed.
Decrease the velocity feedforward coeffi-
cient.
8213 1821 No positive value has been set in the ref-
erence counter capacity parameter.
Specify a positive value in the parameter
listed at the left.