7.6 When time required for acceleration/deceleration increases
(1) Check the parameter setting
(a) Parameter data for each motor model
(b) Limited output pattern and output limit
0 15
15i 16i/16
Description
6528 3028 3028 4028 Sets a limited output pattern.
6529 3029 3029 4029 Output limit
(c) Regenerative power limit (Make sure that the set value is the same
as the one listed in the motor model-specific parameter table)
0 15
15i 16i/16
Description
6580 3080 3080 4080 Regenerative power limit
6930 3310 3166 4166 Regenerative power limit
(for low-speed characteristics)
(2) Check the input signal.
(a) Torque limit command
0 15
15i 16i/16
7 6 5 4 3 2 1 0
G229 G227 G227 G070 TLMHA TLMLA
7.7 Status Error indication function
If a parameter is set incorrectly, or an incorrect sequence is set, the error
LED (yellow) of the indicator section on the spindle amplifier module (SPM)
lights to indicate the corresponding error number.
If the spindle motor malfunctions, check the error number indication on the
amplifier indicator section, then take action to correct the fault as described
in the table below.
Described parameter No. is 16i/16’s.