10. FANUC PANEL i
B–63323EN/03
374
When PANEL i is used, the following environmental conditions (as
measured top of the PANEL i inside the cabinet) must be ensured for the
PANEL i unit installation.
Ambient temperature Operating : +5 to +45_C
Non–operating : – 20 to +60_C
Change in tempera-
ture
Up to 0.3_C/min
Ambient relative
humidity
Standard : 10 to 75% (non–condensing)
Short–term : 10 to 90% (non–condensing)
(within one month)
Vibration Operating : up to 0.5G
Non–operating : up to 1.0G
Environment Installed in a hermetically sealed cabinet
Altitude Operating : – 60m to 3000m
Non–operating : – 60m to 12000m
(*1) Ambient temperature during operation :
The temperature sensor on the PANEL i PCB monitors whether the
temperature is within the specified range.
1) If the temperature at power–on is beyond the allowable range
only CNC/PMC is started. After that if the temperature
becomes to within the allowable range, PANEL i
automatically starts.
This function is disable when Option for Non–Connecting
with CNC is ordered. PANEL i starts up irrespective of the
temperature.
Therefore, the temperature around PANEL i should be
watched by the other method.
2) If the temperature drifts out of the allowable range after
normal activation, an error occurs when the hard disk is next
accessed.
(*2) Vibration :
The PANEL i unit and built–in hard disk drive may suffer resonance
at certain frequencies. Careful checking is required on the PANEL
i unit has been mounted on a machine.
CAUTION
If an operation error or mishap occurs, the data on the hard
disk may be lost, even if all the installation conditions are
satisfied. Therefore, always maintain a backup copy of the
data on the hard disk in case the stored data is lost or
damaged.
Especially, the power–off on accessing the hard disk must
not be done because that possibility is very high. Please
concern for the end–users.
Some development or maintenance options may not satisfy the
above specifications.
10.5
SPECIFICATION
10.5.1
Environment