6. CONNECTION OF I/O UNITS TO
MACHINE INTERFACE
B–63323EN/03
82
DOCOM
ON
OFF
DO when the corre-
sponding DO is on
in the sequence
DO when the cor-
responding DO is
off in the sequence
ON
OFF
ON
OFF
NOTE
If a DO is on in the sequence, the on/off state of the DOCOM
is reflected on that DO as shown in the dotted area. Do not
turn off +24 V supplied to the I/O module during operation.
If it is turned off, an alarm is issued for communication with
the CNC. This +24 V must be turned on at the same time
or before the power to the CNC is turned on. It must be
turned off at the same time or after the power to the CNC is
turned off.
Parallel connection of DO points (output signals)
Connecting two DO points in parallel for simultaneous on/off control in
the sequence can double the maximum allowable DO load current,
allowing up to 400 mA to be obtained, since the maximum allowable load
current of one DO point is 200 mA. Note, however, that when the DO
points are off, their leakage current is also doubled (to up to 40 A).
DOCOM
CB150(01),(33)
DV
+24 V voltage regulator
+24V 0V
DV
Relay