B-64004EN/02 6.PARAMETERS
- 93 -
#7 #6 #5 #4 #3 #2 #1 #0
10500 STP APM AVM
[Input type] Parameter input
[Data type] Bit path
NOTE
When this parameter is set, the power must be
turned off before operation is continued.
# 0 AVM In case that a servo alarm occurs,
0: MCC off signal (*MCFVx) is turned to “0” when some servo
alarm occurs.
1: MCC off signal (*MCFVx) is turned to “0” when any servo
alarm occurs.
In case that this parameter is set to “1”, MCC off signal (*MCFVx) of
all axes, which belong to the same path as the alarm axis, are turned to
“0” when a servo alarm occurs.
# 1 APM In case that a spindle alarm (SPxxxx) occurs
0: MCC off signal (*MCFPs) is turned to “0” when some spindle
alarm occurs.
1: MCC off signal (*MCFPs) is turned to “0” when any spindle
alarm occurs.
In case that this parameter is set to “1”, MCC off signal (*MCFPs) of
all spindles, which belong to the same path as the alarm spindle, are
turned to “0” when a spindle alarm occurs.
# 3 STP When the power is turned on, a MCC off test is:
0: Carried out. (The screen is changed to Dual Check Safety
Diagnosis screen automatically and the warning "EXECUTE
MCC TEST" is displayed at power-on, and MCC off Test
execution request signal (RQT) is output.)
1: Not carried out.