5.I/O SIGNALS B-64004EN/02
- 58 -
Guard Open Request signal (input)
ORQ <PMC: Gn191#3>(for each machine group)
This signal is input when an operator intends to release the guard lock
and open the protective door.
[Classification] Input signal (Single signal)
[Function] In order to open the protective door, this signal requests CNC to
unlock the guard lock with the Dual Check Safety Function. Guard
Open Request signal (ORQ) is not input via the DCS PMC.
0: not request to open guard lock.
1: request to open guard lock
[Operation] When CNC detects that the Guard Open Request signal (ORQ) is 1,
CNC returns Guard Open Inhibit signal (*OPIHB). A machine tool
builder must design the PMC ladder program so that the guard lock is
released after judging the result of safety machine position check,
safety speed check, safety position error check to be safe or other
safety condition such as Dual Check alarm status signal to be safe.
This signal is not a safety signal that is checked doubly. But this is an
important signal to make up the safety system. Then a machine tool
builder must design the proper ladder program to deal with this signal.
IMPORTANT
The mistake of the ladder program cannot be
checked. So be sure to perform the confirmation of
the safety function. (refer to the chapter 7)
Guard State signal (Machine side input signal)
*SGOPN <PMC:X machine side signal><DCS PMC:X machine side signal> (for each safety
door)
Input the guard state of the protective door to this signal. When the
protective door is open (Guard State signal (*SGOPN) =0), set Safety
Check Request signal (*VLDVx, *VLDPs) to “0” in order to activate
the alarm monitoring of safety functions.
[Classification] Input signal (Dual signal)
[Function] Guard State signal informs CNC of the guard open/closed state for the
Dual Check Safety Function.
0: Guard open state
1: Guard closed state
[Operation] When Guard State signal (*SGOPN) is “0”, the ladder program turn
Safety Check Request signal (*VLDVx, *VLDPs) to “0” in order to
activate the alarm monitoring of safety speed, safety machine position
and safety position error. If the ladder program detects abnormal
condition in each CPU, it generates a safety related alarm and stops
motors.
IMPORTANT
As for the contacts for Guard State signal, it is
recommended to fulfill the Standard IEC60947-5-1.