6.PARAMETERS B-64004EN/02
- 100 -
[Example]
Parameter
No.
Setting
value
Output address of position switch signal
13870 00 F755-F756 (1st to 16th position switch)(PMC)
F008-F008 (1st to 16th position switch)(DCS PMC)
13871 01 F757-F758 (17th to 32nd position switch) (PMC)
F009-F010 (17th to 32nd position switch)(DCS PMC)
13872 50 F5755-F5756 (33rd to 48th position switch) (PMC)
F107-F108 (33rd to 48th position switch)(DCS PMC)
13873 71 F7757-F7758 (49th to 64th position switch) (PMC)
F109-F110 (49tht to 64th position switch)(DCS PMC)
NOTE
1 If all setting values are “0”, the output address is
regarded as follows.
Position switch 1 to 16: F755-F756(PMC) /
F007-F008(DCS PMC)
Position switch 17 to 32: F757-F758(PMC) /
F009-F010(DCS PMC)
Position switch 33 to 48: F1755-F1756(PMC) /
F027-F028(DCS PMC)
Position switch 49 to 64: F1757-F1758(PMC) /
F029-F030(DCS PMC)
2 Do not assign two or more position switch to the same
address.
13880 Axis corresponding to the 1st safe position switch
13881 Axis corresponding to the 2nd safe position switch
…
13910 Axis corresponding to the 31st safe position switch
13911 Axis corresponding to the 32nd safe position switch
10501 Axis corresponding to the 33rd safe position switch
10502 Axis corresponding to the 34th safe position switch
…
10531 Axis corresponding to the 63rd safe position switch
10532 Axis corresponding to the 64th safe position switch
NOTE
When this parameter is set, the power must be
turned off before operation is continued.
[Input type] Parameter input
[Data type] Byte
[Valid data range] 0 to Number of controlled axes