B-63164EN/04 APPENDIX A.ALARMS
- 53 -
l
ll
l CNC type differs from HSSB device set value.
Explanation
The CNC Type of the HSSB device set value differs from
the connected CNC.
Action
Change the CNC Type of the HSSB device set value to
the same Type as the connected CNC.
l
ll
l CNC not supported by CNC screen display function is
connected.
Explanation
A CNC not supported by the CNC screen display function
is connected.
Action
Change the CNC, or consider discontinued use of the
CNC screen display function.
l
ll
l Enter host name or IP address.
Explanation
Neither a host name nor IP address is specified in the
destination specification dialog box of the Ethernet
version.
Action
Specify the correct host name or IP address.
l
ll
lEnter port number.
Explanation
No target CNC port number is specified in the destination
specification dialog box of the Ethernet version.
Action
Specify the correct port number.
l
ll
l Enter a timeout value.
Explanation
No communication timeout value is specified in the
destination specification dialog box of the Ethernet
version.
Action
Specify a timeout value (in seconds).
l
ll
l %s is not found.
Explanation
An attempt to connect to a CNC having a host name or IP
address indicated with %s failed.
Action
(1) Check that the CNC is supplied with power.
(2) Check the setting of the FANUC Ethernet board.
(3) Check the TCP/IP setting in the personal computer.
(4) Check the network connection.
(5) If the CNC to be connected has been specified using
a host name, check the setting of the HOSTS file and
DNS server. Alternatively, try to connect using an IP
address.
l
ll
l The signal setting is invalid.
Explanation
No close signal is set in the Close Signal dialog box of the
Ethernet version.
Action
Specify the correct close signal.