B-62924EN/04 OPERATION 1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C
- 27 -
1.2.3 Setting for Address Assignment
Pressing soft key [ADDR] on Screen 1-5 displays Screen 1-7.
By pressing soft keys [PRV.NO] and [NXT.NO], the station number
of a DP-Slave to be set can be changed. To move to the screen of a
desired station number directly, enter the station number, then press
soft key [PRV.NO] or [NXT.NO].
Screen 1-7
CAUTION
When assigning addresses, pay careful attention to the
following points:
1 Assign addresses to all DP-Slaves that are set to
ENABLE in the slave parameters.
2 Be careful not to assign duplicate addresses to a
DP-Slave.
3 Ensure that a specified DI data area, DO data area,
and diagnose data area do not overlap one another.
4 Ensure that the specified addresses do not overlap
an area used for a ladder program.
5 Use the R area only. (When using PMC-SB5, be
careful not to exceed R1499. When using PMC-SB6
or PMC-NB6, be careful not to exceed R2999.)