B–63083EN/02
6. SPINDLE CONNECTION
80
1
3
4
12,14,16
1
Connector JA7B
RECOMMENDED CABLE SPECIFICATION: A66L–0001–0284#10P (#28AWG×10 pairs)
CNC
RECOMMENDED CABLE–SIDE CONNECTOR
PCR–E20FA(Honda Tsushin Kogyo Co., Ltd.)
FI30–20S(Hirose Electric Co., Ltd.)
FCN–247J020–G/E(Fujitsu, Ltd.)
52622–2011(Molex Japan Co., Ltd.)
3
4
2
12,14,16
2
Cable connection
Connector JA41
SOUT
:SOUT
SIN
:SIN
SIN
:SIN
SOUT
:SOUT
Spindle
amplifier
module
GROUNDING
PLATE
GROUNDING
PLATE
NOTE
In the following cases, use optical fiber cable connection
through an optical I/O link adapter.
D When the cable length exceeds 20 m.
D When the power magnetics cabinet where the spindle
amplifier is installed and the operator’s panel cabinet where
the CNC control unit is installed cannot be connected
through a grounding wire of 5.5 mm
2
or more.
D When the cable may be affected by noise.
For instance, this applies when there is a source of strong
magnetic noise, such as a welder, near the cable or when
the cable is routed, for a long distance, in parallel with a
power line or ferroelectric cable which may generate noise.