C.DIFFERENCES FROM THE Series 16i APPENDIX B-63943EN-2/01
- 338 -
Function
Series 16i Series 30i
Program condensation Only the program specified with #8520 #8520=0: The entire program memory is
condensed.
#8520≠0: A specified program is
condensed.
Completion code (#8529) In addition to the completion codes
indicated in the completion code list, there
are completion codes posted with the
same numbers as PS alarm numbers.
Detail completion codes are provided.
No codes other than those indicated in the
list are output.
Special code An increased number of codes are usable.
Cutting period reading and
presetting
Even if presetting is performed,
parameters (Nos. 6753 and 6754) are not
modified.
Both reading and presetting are performed
based on parameter (Nos. 6753 and
6754).
Cutting distance
accumulation along
arbitrary axes only
The first, second, and third controlled axes
only can be selected.
All axes can be selected.
Processing and referencing
P-CODE variables as array
type
Variables #1 to #99 are always array-type
variables.
To use variables #1 to #99 as array-type
variables, set #8518 to 1.
If #8518 is 0, variables #1 to #33 are local
variables, and variables #34 to #99 are
unusable.
Window function
Alarm information
Alarm information modifications have
been made. So, P-CODE source
program need to be modified.
Window function
Diagnosis information
Diagnosis information modifications have
been made. So, P-CODE source
program need to be modified.