B-64174EN/01 PROFIBUS CONFIGURATION TOOL 3.OPERATION
- 81 -
Setting item of "Slave Flag and Slave Type"
Item Description
Slave Flag Set flags for communication with the slave station.
Active Invalid: Does not perform communication with the
slave station.
Valid: Perform communication with the slave station.
New Prm Invalid: Does not transmit new parameter data to the
slave station.
Valid: Transmits new parameter data to the slave
station.
Slave Type Manufacturer-specified type indication for the slave
station
This item need not be edited usually.
Setting item of "General Prm Data"
Item Description
Station Status Set flags for slave operation condition setting.
Lock Req,
Unlock Req
Make either of the settings below.
• When Lock Req = Valid and Unlock Req = Invalid
The parameters of the slave station cannot be
modified from the master station.
• When Lock Req = Invalid and Unlock Req = Valid
The parameters of the slave station can be modified
from the master station.
Sync Req Be sure to invalidate this item.
Freeze Req Be sure to invalidate this item.
Watchdog On Invalid: Disables disconnection detection.
Valid: Enables disconnection detection.
Watchdog Time Set a disconnection detection time.
A disconnection detection time involves two
coefficients as follows:
Coefficient 1 × Coefficient 2 × 10 (Unit: msec)
There is no distinction between coefficient 1 and
coefficient 2.
Coefficient 1 for disconnection detection time
determination
(Coefficient 1)
Range: 1 to 255 (Unit: msec)
Coefficient 2 for disconnection detection time
determination
(Coefficient 2)
Range: 1 to 255 (Unit: msec)
Set a minimum wait time until a response is returned to
the CNC (master).
min T sdr
Range: 0 to 255 (Unit: Bit time)
Group Ident Used for group specification for the
DDLM_Global_Control instruction
G1 to G8 Represents group 1 through group 8. A group
checked is valid.