B-62714EN/04 OPERATION 2.LCD-MOUNTED TYPE 16i/18i/21i-A, Power Mate i-D/H
- 73 -
30106 DI/DO MAP MODE
[Input type] Parameter input
[Data type] Word
[Valid data range] 0 : DI/DO data transfer function
1 : Global I/O transfer function
30107 Maximum slave station number from which data is received by the local
station when the global I/O transfer function is used
[Input type] Parameter input
[Data type] Word
[Valid data range] 0 to 31
0 : The global I/O transfer function is not used.
1 to 31 : The global I/O transfer function is used. Set a maximum
slave station number from which data is received by the
local slave station.
30108 Internal relay address of the start of DO
[Input type] Parameter input
[Data type] Word
[Valid data range] Set 82 as R.
30109 Internal relay offset of the start of DO
[Input type] Parameter input
[Data type] Word
[Valid data range] 0 to 9999
30110 DO byte length
[Input type] Parameter input
[Data type] Word
[Valid data range] 0 to 128(Caution)
Set a DO data area size.
CAUTION
When using the global I/O transfer function, ensure
that the DI data size and DO data size of each slave
station on the network do not exceed 48 bytes.