APPENDIX
B–64115EN/01
A. ALARM LIST
545
(1) PMC ALARMS/SYSTEM ALARMS (PMC–SB7)
Alarm number Faulty location/corrective action Contents
ER01 PROGRAM DATA ERROR 1) Re–input the sequence program.
2) Replace the master printed circuit
board.
The sequence program is invalid.
ER02 PROGRAM SIZE OVER 1) Reduce the sequence program.
2) Contact FANUC to have a larger num-
ber–of–Ladder–steps option speci-
fied.
The sequence program is too large.
The sequence program is invalid.
ER03 PROGRAM SIZE ERROR
(OPTION)
1) Reduce the sequence program.
2) Contact FANUC to have a larger num-
ber–of–Ladder–steps option speci-
fied.
The sequence program exceeds the size
specified by the number–of–Ladder–
steps option.
ER04 PMC TYPE UNMATCH Using an offline programmer, change the
sequence program to that for the correct
PMC type.
The setting of the type in the sequence
program differs from the actual type.
ER06 PMC CONTROL SOFT-
WARE TYPE UNMATCH
Contact FANUC to specify certain PMC
type
The combination of CNC system configu-
ration and PMC type is invalid.
(Example: PMC–SB5 is used for a
3–path CNC system.)
ER07 NO OPTION (LADDER
STEP)
1) Restore the backed up CNC parame-
ter data.
2) Check the data sheet and re–input the
CNC parameters.
3) Contact FANUC to specify a number–
of–Ladder–steps option of the neces-
sary size.
No number–of–Ladder–steps option is
found.
ER08 OBJECT UNMATCH 1) Contact FANUC. An unsupported function is used in the
sequence program.
ER09 PMC LABEL CHECK ER-
ROR PLEASE TURN ON POWER
AGAIN WITH PUSHING ’O’&’Z’.
(CLEAR PMC SRAM)
1) Press and hold down the ’O’ and ’Z’ key
combination, and turn the CNC back
on.
2) When using the loader control func-
tion, power on the CNC again while
pressing the ”5” and ”Z” keys.
3) Replace the backup battery.
4) Replace the master printed circuit
board.
With a change in the PMC type, for ex-
ample, the retention–type memory of the
PMC must be initialized.
ER10 OPTION AREA NOTHING
(xxxx)
Contact FANUC to reconfigure the PMC
management software.
The PMC management software is not
loaded correctly.
ER11 OPTION AREA NOTHING
(xxxx)
Contact FANUC to reconfigure the PMC
management software.
The PMC C board management software
is not loaded correctly.
A.2
LIST OF ALARMS
(PMC)