APPENDIX
B. ALARM LIST
B–62755EN/01
456
Alarm
No.
RemedyDescriptionMeaning
AL–08 High input voltage Detects that switch is flipped to 200 VAC when input
voltage is 230 VAC or higher (models 30S and 40S).
Flip switch to 230 VAC.
AL–09 Excessive load on main circuit
section
Detects abnormal temperature rise of power transis-
tor radiator.
Cool radiator then reset
alarm.
AL–10 Low input voltage Detects drop in input power supply voltage. Remove cause, then reset
alarm.
AL–11 Overvoltage in DC link section Detects abnormally high direct current power supply
voltage in power circuit section.
Remove cause, then reset
alarm.
AL–12 Overcurrent in DC link section Detects flow of abnormally large current in direct cur-
rent section of power cirtcuit
Remove cause, then reset
alarm.
AL–13 CPU internal data memory ab-
normality
Detects abnormality in CPU internal data memory.
This check is made only when power is turned on.
Remove cause, then reset
alarm.
AL–15 Spindle switch/output switch
alarm
Detects incorrect switch sequence in spindle switch/
output switch operation.
Check sequence.
AL–16 RAM abnormality Detects abnormality in RAM for external data. This
check is made only when power is turned on.
Remove cause, then reset
alarm.
AL–18 Program ROM sum check er-
ror
Detects program ROM data error.This check is
made only when power is turned on.
Remove cause, then reset
alarm.
AL–19 Excessive U phase current
detection circuit offset
Detects excessive U phase current detection ciucuit
offset.
This check is made only when power is turned on.
Remove cause, then reset
alarm.
AL–20 Excessive V phase current
detection circuit offset
Detects excessive V phase current detection circuit
offset.
This check is made only when power is turned on.
Remove cause, then reset
alarm.
AL–24 Serial transfer data error Detects serial transfer data error (such as NC power
supply turned off, etc.)
Remove cause, then reset
alarm.
AL–25 Serial data transfer stopped Detects that serial data transfer has stopped. Remove cause, then reset
alarm.
AL–26 Disconnection of speed detec-
tion signal for Cs contouring
control
Detects abnormality in position coder signal(such as
unconnected cable and parameter setting error).
Remove cause, then reset
alarm.
AL–27 Position coder signal discon-
nection
Detects abnormality in position coder signal (such
as unconnected cable and adjustment error).
Remove cause, then reset
alarm.
AL–28 Disconnection of position
detection signal for Cs con-
touring control
Detects abnormality in position detection signal for
Cs contouring control (such as unconnected cable
and adjustment error).
Remove cause, then reset
alarm.
AL–29 Short–time overload Detects that overload has been continuously ap-
plied for some period of time (such as restraining mo-
tor shaft in positioning).
Remove cause, then reset
alarm.
AL–30 Input circuit overcurrent Detects overcurrent flowing in input circuit. Remove cause, then reset
alarm.