B-65272EN/04 SPECIFICATIONS FOR THE αi SERIES 4.NOTES ON INSTALLATION
- 19 -
4.2 POWER LEAD CONNECTION
WARNING
To attach the power leads and jumpers, follow the procedure
described in this section to make connections with specified torque.
Driving a motor with terminals loosened could result in the terminal
board overheating and causing a fire. In addition, it may remove
terminal to cause a ground fault, short circuit, or electric shock.
CAUTION
1. When attaching the power leads and jumpers to the terminal
board of a motor, tighten the screws with torque specified in the
table. For the terminal size of a terminal board, refer to Chapter
4, "CONNECTIONS" in the manual of the corresponding series.
Terminal size
Tightening torque
[N⋅
⋅⋅
⋅m]
M4 1.1 to 1.5
M5 2.0 to 2.5
M6 3.5 to 4.5
M8 8 to 10
M10 15 to 16
2. To maintain the required isolation distance, observe the
following:
• When attaching a crimp terminal at the end of a power lead,
cover the crimped portion of the crimp terminal with
insulating tube.
• If the terminal board is provided with an insulating cover,
fasten the power leads with the screws, and then put back
the insulating cover in place.
3. If you want to energize an output switching type motor only with
the low- or high-speed winding rather than switching its output,
jumper the low- or high-speed winding, whichever is applicable,
and then connect three power leads (the U-, V-, and W-phase
wires) to the motor (except for the α15/12000i
T and αiL series
motors).
The output switching type motors in the αi series, αi
P series, and
α(HV)i
P series come standard with jumpers in the terminal box.
If you want to any other output switching type motor, place an
order for jumpers according to the following list.