3. SPECIFICATION
9
Table 3.1 (a) Specification (Common)
Item
Specification
Power
supply
Three–phase input
for power
(Caution 1)
Voltage : 200/220/230 VAC +10 %, –15 %
Frequency : 50/60Hz " 2Hz
Voltage deviation due to load (at maximum
output)
shall be 7% or less.
Single–phase input
for control power
(Caution 1)
Voltage : 200/220/230 VAC +10 %, –15 %
Frequency : 50/60Hz " 2Hz
Single–phase input
emergency stop
(Caution 2)
Voltage : 100 VAC +10 %, –15 %
Frequency : 50/60Hz
Voltage : 110 VAC +10 %, –15 %
Frequency : 60Hz
Control of main circuit Sine–wave PWM control by transistor bridge
(IPM)
Alarm and protection func-
tions
· Over–voltage alarm
· Low control power voltage alarm
· Low DC link voltage alarm
· Regenerative discharge control circuit
failure alarm
· Over–regenerative discharge alarm
· Dynamic brake circuit failure alarm
· Over–current alarm
· IPM alarm
· Circuit breaker
Contact of the relay of the Dy-
namic brake circuit
(Caution 3)
D Except SVU1–130, SVUC1–130
· In dynamic brake, its contact is short.
· Condition to use the contact
24VDC, more than 10mA less than 0.3A
D SVU1–130, SVUC1–130
· In dynamic brake, its contact is open.
· Condition to use the contact
24VDC, more than 10mA less than 0.3A
CAUTION
1 Two lines of the three–phase input for power were
connected with the lines of the single–phase input for
control power by a jumper bar at the factory.
2 Necessary for the SVUC only
3 The customer can use this contact for monitoring purposes
when designing a safety protection circuit.
3.1
SPECIFICATION