9. CONNECTION
B–65192EN/02
62
CAUTION
1 Be sure to use an AC line filter to reduce effect of harmonic
noise to the power supply. Two or more SVUCs can be
connected to one AC line filter if its power supply capacity
is not exceeded.
2 RC and RI were connected with each other through a
jumper bar at the factory. If a separate regenerative
discharge unit is to be used, remove the jumper bar.
3 TH1 and TH2 were connected with each other through a
jumper bar at the factory. Remove the jumper bar, and
connect them to the separate regenerative discharge unit
and power transformer thermostat.
4 Only the A06B–6090–H008 has FAN1 and FAN2. Connect
them to the fan motor of the separate regenerative
discharge unit.
NOTE
1 The unit should use 100 VAC for emergency stop, in the
same way as the C series amplifier.
2 L1C and L1 were connected with each other through a
jumper bar at the factory, and so were L2C and L2.
3 Some NC units do not require a relay unit. For details, refer
to the appropriate NC connection manual.
4 The SVUC connectors and terminal block indicated in
parentheses, ”( )”, correspond to 2–axes amplifier.