3. TROUBLESHOOTING AND
B-65235EN/02 TROUBLESHOOTING AND RECOVERY RECOVERY PROCEDURES
- 67 -
3.3.5
Invalid Servo Parameter Setting Parameters
The following table contains actions to be taken for invalid
servo parameter setting alarms.
Alarm Decision criterion Adjustment
item
POA1 overflow Try resetting POA1 to 0
Parameter: No.8X47-2047=0
Adjustment1
1 pulse suppression
level overflow
Disable the pulse suppression function.
Function bit:No.8X03-2003, B4=0
Adjustment2
Feed-foward
coefficient overflow
Reset the feedfoward coefficient to 0
Parameter: No.8X68-2068=0
No.8X92-2092(advance)=0
Adjustment3
Position gain
overflow
Reset the position gain to 0
Parameter: No. 517-1825= 0
Adjustment4
Number of position
pulses overflow
The number of position pulses is
greater than 13100
(No. 8X00-2000,B0)
Adjustment5
Motor type No. Check whether the setting is correct.
Parameter: No. 8X20-2020
Adjustment6
Invalid axis
selection
parameter setting
Check whether the axis assignment is
correct.
Series 0-C: No. 269 to 274
Series 16, 18, 20, 21 Power Mate:
No.1023
Others
Number of position pulses ≤ 0
Number of velocity pulses ≤ 0
Direction of travel = 0
Feed gear numerator ≤ 0,
denominator ≤ 0
Numerator > denominator
(Serial A, α and semi-closed mode)
NOTE
The parameter numbers in the table are in the following
order:
No. (Series 0-C)-(Series 16, 18, 20, 21)