9.TOTAL CONNECTION DIAGRAM SVM B-65322EN/02
- 76 -
NOTE
1 The ground plate to which the shield is connected
must be placed as close as possible to the servo
amplifier so that distance between the ground plate
and the servo amplifier becomes shortest.
2 In case that the cable is prepared by the user, the
total resistance (round trip) of 5 V and 0 V must be
less than 0.8 Ω.
3 The maximum applicable wire diameter of the cable
connector on the motor side is 0.5 mm
2
(when
crimping tool 1463475-1 is used) or 0.85 mm
2
(when crimping tool 1276654-1 is used).In case of
using thicker wire or cable, take measures
described below.
Connector
Servo
am
lifie
Servo motor
The total resistance (
ound
trip) of 5 V and 0 V must be
less than 0.8
.
4 In case of incremental Pulsecoder, 6 V is not
necessary to be connected.