9.TOTAL CONNECTION DIAGRAM I/O Link B-65322EN/02
- 218 -
NOTE
1 Place the grounding plate to which the shield is
connected at a nearby position of the βi SVM to
minimize the distance between the βi SVM and the
grounding plate.
2
In case that the cable is prepared by MTB, total resistance of
5V and 0V must be less than 2Ω.
3
Pulsecoder side connector can accept maximum 0.5mm
2
(wire construction 20/0.18 or 104/0.08, insulation outer
diameter
φ1.5 or less) wire and sheath diameter is φ5.7 to
φ8.0. In case of using thicker wire or cable, take measures
described below.
The total resistance (round
trip) of 5 V and 0 V must be
less than 2
Ω
.
[Case 1] Cable conductor exceeds 0.5mm
2
. [Case 2] Sheath diameter of exceeds
φ
8.
Soldering or crimping
Servo motor
SVM
Connector
Cable thicker than
φ
8
SVM
Servo motor
The total resistance (
ound
trip) of 5 V and 0 V must be
less than 2
Ω
.
4
In case of incremental Pulsecoder, 6V is not necessary to be
connected.
• Crimp tool specification
A06B-6114-K201/JN1E : For 0.18mm
2
or 0.3mm
2
A06B-6114-K201/JN1D : For 0.18mm
2
or 0.5mm
2
• Connector kit specification
A06B-6114-K204/S : Straight plug (including a contact)
A06B-6114-K204/E : Elbow plug (including a contact)
• Recommended cable
A66L-0001-0479 : Flexible cable 28 m or less long
A66L-0001-0488 : Flexible cable 50 m or less long
9.2.4.2 Servo motor βis series (β0.2/5000is, β0.3/5000is)
See Subsection 9.2.4.2 "Servo motor βis series (β0.2/5000is,
β0.3/5000is)" in Part I.