3.SPECIFICATIONS SVPM B-65322EN/02
- 106 -
3.2 COOLING FAN MOTOR
Install a cooling fan motor listed below.
Otherwise, make arrangements so that the required air flow can be
obtained.
Ordering number Optional fan Required air flow
SVPM2-5.5i
A06B-6134-H201#*
SVPM3-5.5i
A06B-6134-H301#*
A06B-6134-K001
One unit
SVPM2-11i
A06B-6134-H202#*
SVPM3-11i
A06B-6134-H302#*
A06B-6134-K001
One unit
SVPM2-15i
A06B-6134-H203#*
SVPM3-15i
A06B-6134-H303#*
A06B-6134-K001
One unit
2 m/s
3.3 HOW TO OBTAIN A POWER SUPPLY CAPACITY
- Output capacity -
The output capacity is the sum of the total spindle motor
continuous output rating multiplied by a coefficient (1.15) and
the servo motor continous output rating multiplied by a
coefficient (0.6).
-Power supply capacity-
SVPM*-5.5i
Power supply capacity (kVA) = output capacity (kW) × 1.64
SVPM*-11i
Power supply capacity (kVA) = output capacity (kW) × 1.55
SVPM*-15i
Power supply capacity (kVA) = output capacity (kW) × 1.47
[How to obtain the input current so units to be installed at the
input section can be selected]
Obtain the SVPM input current, using the following expression.
Use it as a reference value in selecting a circuit breaker, magnetic
contactor, and power cable.
(Margin for selection: 1 to 1.5 times)
(margin)2.1
)( tagesupply volpower nominal3
)(capacity supply Power
)(current input ×
×
=
Vrms
kVA
ArmsSVPM
(Assume the nominal power supply voltage (Vrms) is usually
200 Vrms.)