Option slot
Total amount of
generated heat
2 slots 26W
3 slots 38W
4 slots 38W
Unit
Amount of
generated
heat
Remarks
MDI unit 0W
Operator’s panel I/O module 12W (NOTE 1)
Connector panel I/O module (basic) 8W (NOTE 1)
Connector panel I/O module (expansion) 5W (NOTE 1)
Separate detector interface unit
9W Only for unit with four ba-
sic axes
Separate detector interface unit
14W Four basic axes and four
additional axes (NOTE 2)
NOTE
1 This value applies when 50% of the module inputs are on.
2 The amount of heat generated in the separate detector is
not included.
NOTE
1 The amount of heat generated in the LCD and MDI units is
included, but that in each option board is not.
2 The amount of heat generated in the ISA expansion board
varies from one model to another. Add the amount of heat
generated in the ISA board to be used.
3 The amount of heat generated in the ATA flash card may
vary depending on its memory capacity, changes made to
the card specification, and other factors.
4 When using option boards, keep the total amount of heat
generated in the selected option boards to within the
corresponding value listed in the following table.
GFKE-0222-EN
2. LCD–MOUNTED TYPE i SERIES
HARDWARE
244