B-63644EN/02 V. CONNECTION 2.SETTING
- 293 -
2.1 ENVIRONMENTAL CONDITIONS FOR INSTALLING A CNC
A CNC in which an Fast Ethernet board or Fast data server is installed
must be used in the following environment.
Condition
Fast Ethernet board
Fast data server
Operation (Note 2)
0°C to 55°C
(0°C to 58°C)
Ambient
temperature
Storage or
transportation
-20°C to 60°C
Humidity
Relative humidity 30% to 95% or less
No condensation
Operation 0.5 G or less
Vibration
Non-operation 1.0 G or less
Operation Up to 1000 m
Altitude
Non-operation Up to 12000 m
Contaminants
Ensure that the control unit is not exposed to
contaminants (dust, coolant, organic
solvents, acid, corrosive gas, and salt).
Ionized (or non-
ionized) radiant
ray
If the control unit is exposed to radiant rays
(microwave, ultraviolet ray, laser beam, X
ray, and so forth), use a protective shield.
CAUTION
Even if a control unit is installed in the environment
described above, the contents on the ATA flash card
may be destroyed as a result of a misoperation or
unexpected event. This tends to happen if the power
is turned off while accessing the ATA flash card. An
accident can occur. So, ensure that the data on the
ATA flash card is backed up at all times.
NOTE
1 The installation environment for control units
described above assumes that the Fast Ethernet
board and Fast data server are inserted into the
CNC. If the installation environment for the CNC is
severer than the installation environment above, the
installation environment for the CNC takes
precedence. In such a case, check the connection
manual of the CNC used.
2 The values enclosed in parentheses apply to the
Fast Ethernet board and Fast data server for the
LCD-mounted type Series16i/18i/21i.