B-63003EN-2/01 Chapter 2 Configuring the 16i/18i/21i 2 - 3
2
Entering Parameter Values from the MDI Panel
First, let’s briefly go over the notation used in this manual. Hard keys are those keys which are
located on the MDI panel. They will be designated by square brackets [ ]. Soft keys,
meanwhile, are located in a single row directly beneath the LCD. They will be designated by
parentheses ( ).
In order to set parameter values after initial power-up, use the following procedure:
1. Press [SYSTEM]. The alarm messages should be replaced by
the parameter screen.
2. If the parameter screen does not appear, press (PARAM) and it will appear.
3
.
For a bit-type parameter, cursor over to the bit you would like to set using the [←],
[→], [↑], and [↓] hard keys. Then press [1] followed by [INPUT].
4
.
For a word-type parameter, simply enter the numerical value using the MDI panel and
then press [INPUT].
To display the specific parameter which you are looking for on your screen, you can do one of
two things:
1
.
Enter the parameter number from the MDI panel. This will give you a (NO. SRH) soft
key option. Press this and the display should show the specified parameter.
2
.
Use the [PAGE ↑] and [PAGE ↓] keys to scroll to the parameter you are searching for.
However, if the parameters are numerically far apart, this can tend to be cumbersome.