B-65282EN/05 9.CONNECTION
- 185 -
9.3.1.6 Details of cable K7
Cable K7 is used to supply an emergency stop signal to the power
supply module.
Emergency stop
contact
Cable specification:
Two-conductor polyvinyl heavy-duty power cable (JIS C3312),
conductor size of 1.25 mm
2
(50/0.18), PVC sheath 9.6 mm in
diameter
Connector specification:
Tyco Electronics AMP connector with receptacle housing
1-178128-3 and receptacle contact 1-175218-2
(1) When the contact is ON (closed), the spindle motor and servo
motor are enabled.
When the contact is OFF (open), the external magnetic contactor
(MCC) is in the off state, and the spindle motor and servo motor
do not operate.
(2) When the contact is set to OFF (open) during motor rotation, the
spindle motor decelerates, then stops, and the servo motor is
stopped by the dynamic brake.
(3) The contact input signal is specified as follows:
<1> As the external contact capacity, a voltage of at least 30
VDC and a current of at least 100 mA are required.
<2> Significant levels (with the voltage between input pins)
when the contactless signal input mode is used:
Low level "logic 0": Up to 2 V
High level "logic 1": At least 20 V
(4) When the PSM main power is turned off for safety in such a case
that the machine protection door is open, the contact of the ESP
signal (CX4), which is input to the PSM, must be set to OFF
(open) within 200 ms after turn-off of the PSM main power.
When the contact of the ESP signal (CX4) remains ON (closed)
after the PSM main power is turned off, a DC link low-voltage
alarm (alarm No. 4) occurs in the PSM.