Prevention of Gravity Axis Drop
at Power Failure
in αi series servo system
B-65282EN/05-03
Add newly S.Hanyu 04.11.22 01
Table 1. Constant n for SPM and SVM
Amplifiers Model n
SPM-2.2i ~30i, 5.5HVi ~45HVi (60mm/90mm/150mm width type)
1
SPM
SPM-45i, 55i, 75HVi, 100HVi (300mm width type)
1.5
SVM1-20i ~160i, 10HVi ~80HVi (60mm/90mm width type)
1
SVM1-360i, 180HVi (150mm width type)
1.5
SVM1
SVM1-360HVi (300mm width type)
2
SVM2 All models 1.5
SVM3 All models 2
Table 2. The time to keep the control power supply for amplifiers
and constant N (the total of constant n)
The time to keep the control
power supply for amplifiers
N
20msec 8
30msec 6.5
40msec 5
50msec 4
60msec 3
70msec 2
Note) In case that the input voltage is AC200V.
Confirm at the real machine
The time calculated by the above method is rough estimation. So confirm that the
time to keep the control power for both amplifiers and NC at the real machine by all
means. Refer to Section 6 about the method of confirmation.
Countermeasure in case that the time to keep the control power supply for amplifiers is
shorter than “Operate time of brake”.
(1) It is possible to extend the time to keep the control power supply for amplifiers by
supplying the control power for some amplifiers from the external power supply
equipment because the load rate of the control power supplied from PSM is reduced.
Refer to Section 7 about the method of supplying the control power from the external
power supply equipment
(2) In case that it is difficult to add the new control power supply equipment or to replace
the control power supply equipment to large rated current type, it is possible to extend
the time to keep the control power supply for NC and amplifiers by using UPS.